Page 9Installation
Cooling Delta Stage 1 ON
Range: 1 - 8 degrees
Default: 1
Sets the delta from setpoint that stage 1 cooling
starts.
Cooling Delta Stage 1 OFF
Range: 0 - 8 degrees
Default: 0
Sets the delta from setpoint that stage 1 Cooling
stops. Stage 1 turns off at setpoint - Delta Stage 1
Cooling Delta Stage 2 ON
Range: 1 - 8 degrees
Default: 2
Sets the delta from setpoint that stage 2 cooling
starts.
Cooling Delta Stage 2 OFF
Range: 0 - 8 degrees
Default: 0
Sets the delta from setpoint that stage 2 Cooling
stops. Stage 2 turns off at setpoint -Delta Stage 2.
Max Heat SP
Sets the maximum heating setpoint value. Will not ramp or accept setpoints higher that this maximum.
Range: 40F to 109F (4C-43C) Default: 90F (32C)
Min Cool SP
Sets the minimum cooling setpoint value. Will not ramp or accept setpoints lower than this minimum.
Range: 44F to 113F (6C-45C) Default: 60F (15C)
Minimum Run Time (MRT)
Sets the minimum run time before a heating/cooling cycle can turn off. Sets heating/cooling cycle time. Prevents rapid
cycling.
Range: 1 - 9 minutes Default: 3
Minimum Off Time (MOT)
Sets the minimum off time before another heating/cooling cycle can begin. Provides compressor short cycle protection.
Range: 5 - 9 minutes Default: 5
Temp Response
Adjust the temperature sensor sensitivity. Sets how fast the sensor responds to change.
Range: 1 - 6 Default: 2
Fan Cycler
The fan cycler function cycles the HVAC system fan for an ON period followed by an Off period continuously. Used
to provide minimum air ventilation requirements. When the Fan ON time is set to a value greater than 0, an additional
“Cycler” FAN mode is present when pressing the FAN button.
Fan ON Time
Range: 0 - 120 minutes
Default: 0 (=OFF)
Fan OFF Time
Range: 10 - 120 minutes
Default: 10